Features
Mounting Options include either Panel mount or 19" Rack Mount (3U or 4U) , Single or Dual Units
Audible Alarms for +/- Ground Faults, Hi Bat VDC, Low Bat VDC, Open Battery (Ripple voltage), and Loss of AC to Charger
Alarm Delay 1-60 Seconds
Alarm Reset can be Manual or Remote Contact Closure
Mode Selection from Display for Scanning
I420mA Analog Output is standard with 0-1mA Output or Serial Communication RS485 DNP3.0/Modbus Options
Ground Fault Locator and Corrosion Detection Options
ANSI C37.90 - 1974 (Surge Withstand) Compliant
IEC 61000-4-3 (EMC)
SPECS
Contact Ratings: 28VDC, 25mA @125VDC
Voltage Indication: 0 to 199.9
Voltage Accuracy: +/- 0.2VDC
Display Ranges: Battery VDC +/- Bus to Ground, Ground Fault Voltage
Operating Temperature Range: -4 degrees F to 131 degrees F (-20 degrees C to 55 degrees C)
Battery Input: 50 to 180 VDC, 3VA, 125V Battery
Ground Resistors (+/- Bus to Ext Ground) @ 30.82 kOhms
Input Voltages available: 24VDC, 48VDC, 125VDC, 250VDC
Resources
Model Variations
25-1000-125A Battery Monitor, I420/DNP/Modbus/125vdc
25-1000-125B Battery Monitor, I01/DNP/Modbus/125vdc
25-1000-24A Battery Monitor, I420/DNP/Modbus/24vdc
25-1000-24B Battery Monitor, I01/DNP/Modbus/24vdc
25-1000-48A Battery Monitor, I420/DNP/Modbus/48vdc
25-1000-48B Battery Monitor, I01/DNP/Modbus/48vdc
25-1000-250A Battery Monitor, I420/DNP/Modbus/250vdc
25-1000-250B Battery Monitor, I01/DNP/Modbus/250vdc
25-1000-125A-PB Battery Monitor, Pigtail/I420/DNP/Modbus/125vdc
25-1000-125B-PB Battery Monitor, Pigtail/I01/DNP/Modbus/125vdc
25-1000-48A-PB Battery Monitor, Pigtail/I420/DNP/Modbus/48vdc
25-1000-48B-PB Battery Monitor, Pigtail/I01/DNP/Modbus/48vdc
15-1000-125A-1 19" 4U Rack-Mounted One Meter/I420/DNP/Modbus/125vdc
15-1000-125B-1 19" 4U Rack-Mounted One Meter/I01/DNP/Modbus/125vdc
15-1000-48A-1 19" 4U Rack-Mounted One Meter/I420/DNP/Modbus/48vdc
15-1000-48B-1 19" 4U Rack-Mounted One Meter/I01/DNP/Modbus/48vdc
15-1000-125A-2 19" 4U Rack-Mounted Two Meters/I420/DNP/Modbus/125vdc
15-1000-125B-2 19" 4U Rack-Mounted Two Meters/I01/DNP/Modbus/125vdc
15-1000-48A-2 19" 4U Rack-Mounted Two Meters/I420/DNP/Modbus/48vdc
15-1000-48B-2 19" 4U Rack-Mounted Two Meters/I01/DNP/Modbus/48vdc
Accessories
25-1100-GF Ground Fault Hand Held Detector
25-1100-H1 High Impedance CT
25-1100-H2 High Impedance CT and Ripple Generator