CIM
CONTROL INDICATOR MODULE
4. SCADA Out (amber) LED: Indicates the state of operation of the external interface to
the SCADA system. If the LED is ON the SCADA interface is disabled. If the LED is OFF
the SCADA interface is active.
Monitors/Indicators:
The CIM will provide visual indication of the functions monitored by the unit. These include
breaker contact status (open-close), breaker coil status (continuity, tests for open circuit) and
operational state of both the Reclose function and the interface to remote SCADA signals. The
following describes each of the four indicator LEDs located on the front panel of the CIM unit.
1. Breaker Open (green) LED: Indicates the physical state of the breaker (either
open or close). In addition this LED provides visual indication of which device caused
the trip signal for the breaker. A steady "ON" LED indicates a trip signal from any pro-
tective relay device, a rapid flashing LED indicates a trip signal from SCADA, and a
slow flashing LED indicates a trip signal from the manual control switch located in the
CIM unit.
2. Trip Coil Monitor (red) LED: Indicates the continuity (tests for an open circuit) of the
breaker trip coil. The CIM electronics continuously check the continuity of either a single,
dual, or ganged single trip coils (a field programmable dipswitch located within the CIM
selects what type of breaker coil is to be monitored). If the LED is ON the coil is satis-
factory. If the LED is OFF the coil has failed.
3. Reclose Out (amber) LED: Indicates the state of operation of the external
reclose relay. If the LED is ON the relcose relay is disabled. If the LED is OFF
the reclose relay is enabled.
1.
3.
2.
4.
Reclose Enable/Disable Switch
SCADA Enable/Disable Switch
Manual Fail-Safe Switch
Panel Locking Device