This page must be viewed with IE4 or above, and with Active Scripting enabled.
PRIM
Protective Relay Indicator Module
Applications
The PRIM (Protective Relay Indicator Module) is a complete system designed to enhance
transformer protection schemes. It can simultaneously monitor up to four sudden pressure
protective relays, trip up to four breakers and provide latching indication of the fault source.
Features
Accepts Inputs from up to Four Protective Devices
Simultaneously Trips up to Four Circuit Breakers
Visual Status Indication of Circuit Breaker Trip Sources Bright LEDs
Dual Change of State Required False Trigger Protection
Automatic and Manual Modes
Built-in Test Switch Allows Circuit Isolation for Start-Up and Test
19" Rackmountable
Benefits
High Speed Trip Response
SCADA Compatible
One Device Performs the Function of Many
Eliminates Accidental Trips
Can be Reset Locally or Remotely
Conserves Panel Space
Specifications
Input Voltage - 125 VDC
Output Voltage - N/O Contact @ 125VDC @10 amp
Control Power Requirements - Logic: 125VDC @ 100 Milliamps
- LOR/ER 125VDC @10 Amps Nom.
Ambient Temperature - 0°C to +55°C
Physical Size - 19.00"W x 5.25"H x 9.75"D
Ordering Information
Model #
Description
650-100
Protective Relay Indicator Module
Description
The PRIM is an automatic monitoring and control device that accepts inputs from up to four
protective relays (either electronic or electro-mechanical) to provide trip capability for as many
as four circuit breakers. Using the information from the protective relays, the PRIM can
simultaneously trip the four circuit breakers should a fault be detected. In addition, the
PRIMs electronic logic activates one of four front mounted LEDs to provide visual indication of
the specific protective relay that first initiated the trip operation. This LED remains "ON" until
such time that the fault has been cleared from the input device and a reset command is
provided.
An intelligent electronic device, the PRIM is equipped with logic circuitry that protects
against false trigger signals due to accidental shorting or opening of an input contact. This
circuitry requires that each of the external protective devices must have two changes of
state prior to allowing a trip signal. In other words, the device must detect a complete change
of state on both input contacts, i.e., the Normal Open (N/O) contact must change to Normal
Close (N/C) and the Normal Close (N/C) contact must change to Normal Open (N/O).
LEDs replace up to four target relays.